FIREBAN GLASS

Safety from Fire

Insulating glass unit with standard and high performance glazing for sun control, UV control and thermal insulation.

FIREBAN products offer an ideal combination to ensure practical and personal fire safety for periods right up to 120 minutes.

These products are based on tempered safety glass with enhanced mechanical strength, classified as impact safety glass both to the new European Standard EN 12150 and to other relevant national standards, or as laminated safety glass for use where changes in temperature level are involved. Thus FIREBAN E/EW/EI are ideal to install where there is high pedestrian traffic.

FIREBAN quality meets efficiency

Wherever in the world you install glass, your work needs to confirm to Standards. e.g. EN, BS, ASTM, NFPA. Whether in doors, in partitions or in façade glazing, it’s good to know that it has the pedigree to meet these various requirements.

Top-rate light transmission
Best possible size/weight ratio
Excellent sound attenuation
Class EW radiation control down to no more than 10 kW/m2 even after 120 minutes
Extended fire resistance times
Pane size approval up to 5m2

FIREBAN External Quality Control/CE Marketing

FIREBAN products are ‘supervised building components’ in that they are manufactured to a strict regime of quality, both internally and also by independent international Test Authorities. This means that every single pane bears a permanent stamp, indicating manufacturer, product name, pane thickness and fire classification.

FIREBAN also conforms to the requirements for CE-Marking under System 3/EN 12150-2.

FIREBAN PRODUCT RANGE
FIREBAN E/EW

Depending on the building application, we offer under this heading both Class E and Class EW products for up to 60 minutes of fire protection, classified under EN 13501-2.

FIREBAN E Single
5-12mm
Laminated
10-12mm
Insulating
>20mm
E 30 x x x
FIREBAN E Single
5-12mm
Laminated
10-12mm
Insulating
>20mm
E 30 x x x
E 60 x x x
EW 30 x x x
EW 60 x x x
FIREBAN EI

Here you can have clear fire protection with full thermal shielding. Tested internationally and fully certified to EN 13501-2, FIREBAN EI sets new quality standards in terms of interlayer technology, impact safety, sound attenuation, optical clarity and excellent light transmission where a Class EI product must be specified.

FIREBAN E Single
16-47mm
Laminated
18-49mm
Insulating
>29mm
EI 30 x x x
EI 60 x x x
EI 90 x x x
EI 120 x x x

For precise manufacturing sizes, production options, certification and framing system details please extract from our international component listing the data which relates to your own country or contact us for full brochures and product data sheets.

Overview of FIREBAN EW and FIREBAN EI

Here is your introduction to the technical benefits available when you use our products for either internal or external applications. All the data below is to be taken as applying to the finished installation, i.e. frame, glass and glazing materials – naturally the final installed location also plays a part.

Thickness of Glass (mm) Thickness of Element (mm) Interlayer (mm) Spacer(mm) Light Transmission in % G-Value in % Sound Reduction in dB U-Value in W/m2K Max.size of Production in cm Min.size of Production in cm Min. Area Calculation in m2 Weight in kg/m2
SINGLE COMPOUND
FIREBAN EW
120/13-2
5/5 13 3 - 88 85 36 5.8 180 x 300 25 x 35 0.30 29.0
A 0 5/5 13 3 - 88 85 36 5.8 180 x 300 25 x 35 0.30 29.0
FIREBAN EI
30/16-2
5/5 16 6 - 85 67 38 5.0 180 x 300 25 x 35 0.40 34.0
FIREBAN EI
30/16-3
5/4/5 24 5 - 83 65 40 5.0 180 x 280 25 x 35 0.40 52.0
FIREBAN EI
30/16-3
5/4/5 24 5 - 83 65 40 5.0 180 x 280 25 x 35 0.40 52.0
FIREBAN EI
90/15-4
5/4/4/5 33 5 - 80 63 43 5.0 180 x 250 25 x 35 0.40 68.0
A 60 5/5/5 25 5 - 83 65 43 5.0 180 x 250 25 x 35 0.40 54.5
DOUBLE GLAZING
FIREBAN EW
120/13-2
5/5/6 >25 3 >8 82 83 38 3.0 180 x 300 25 x 35 0.30 44.0
FIREBAN EI
30/16-3
5/4/5/5 >37 5 >8 65 59 41 2.0 180 x 280 25 x 35 0.40 55.0
FIREBAN EI
30/16-2
5/5/5 >29 6 >8 71 59 39 2.0 180 x 300 25 x 35 0.40 47.0
Basic Standards:

Proven fire testing in accordance with National and European Standards EN 1363/1364 plus Certification to EN 13501-2. The up-to-date list of approved glass dimensions of each product for each country is available on request.

CE-Marketing:

All Fireban products conform to the requirements for CE-Marketing as per System 3/En 12150-2.